Extinguishers have to be kept in working order under the Fire Safety Order. The British Standard for maintaining them, BS 5306-3, sets the routine almost everyone follows:
- a visual check every month by someone on site;
- a service every year by a competent person;
- an extended service every five or ten years, depending on the type.
The monthly check
Takes a couple of minutes per building. For each extinguisher, check that it is:
- in its proper place, on its bracket or stand, and not blocked;
- the right type for the risk nearby, with its sign;
- showing the pressure needle in the green, if it has a gauge;
- sealed, with the safety pin and tamper seal intact;
- undamaged: no dents, corrosion or split hose;
- in date on its service label.
Anything wrong, take it out of use and call the servicing company. If one has been used, even partly, it needs recharging or replacing.
The yearly service
Done by a competent engineer, usually from a fire protection company. They check each extinguisher inside and out, weigh or check the pressure, replace seals and pins, and fill in the service label. They should leave a report listing every extinguisher, its location and the result, and advise if any are the wrong type or missing.
Extended service and replacement
| Type | Extended service |
|---|---|
| Water, foam and powder (stored pressure) | A discharge test every five years, and refill. |
| Carbon dioxide (CO₂) | An overhaul and pressure test every ten years. |
| Wet chemical (kitchens) | A discharge test every five years. |
Often it’s cheaper to replace an old extinguisher than to extended-service it. The engineer will say which.
The right types
- Water or foam for paper, wood and fabric. Foam also covers flammable liquids.
- CO₂ by electrical equipment such as the stage, the sound desk or the office.
- Wet chemical where there’s a deep fat fryer.
- A fire blanket in the kitchen, checked monthly with the extinguishers.
Your fire risk assessment says how many you need and where. Volunteers and hirers aren’t expected to fight a fire; extinguishers are for getting out safely or putting out something small.
The records to keep
- A log of monthly checks: date, who checked, anything found.
- The engineer’s yearly service report.
- Any extinguishers replaced, discharged or taken out of use.
Our free extinguisher check log gives you a year of monthly ticks for each one.
Common questions
- How often should fire extinguishers be checked?
- Look at them monthly, which anyone on site can do, and have them serviced yearly by a competent engineer, following BS 5306-3.
- Can a volunteer service fire extinguishers?
- A volunteer can do the monthly visual check. The yearly service needs a competent person, usually from a fire protection company.
- How long do fire extinguishers last?
- There's no fixed expiry, but water, foam and powder extinguishers need a discharge test every five years and CO2 extinguishers an overhaul every ten. Replacing them is often cheaper.
- Do we need a fire blanket in the hall kitchen?
- Usually, yes. Your fire risk assessment will say. Check it monthly with the extinguishers.
Extinguishers, never out of date
The Venue Record reminds whoever does the monthly visual check, files the service report when you hand it over, and tells you before the annual service is due.
Set up extinguisher remindersSee it working first
No card needed to start. Then from £19 a month per building.
A plain-English summary for the people who run community buildings, not legal advice. Where your own fire risk assessment, lease, licence or insurer says something different, follow that.