Guide

Safety records a hotel or B&B has to keep

The one kind of venue where the people at risk are asleep. Fire, gas, water and the lift all ask for records with dates on. Here is the list.

Written for owners and general managers and reviewed by The Venue Record in November 2026 against the Home Office sleeping accommodation guide, the Gas Safety Regulations and HSE ACoP L8. Not legal advice.

A hotel, guest house or B&B is the one kind of venue where the people at risk are asleep. That single fact raises the fire safety standard above a shop or a hall, adds a legal interval to the gas safety check, and brings in water safety because guests use showers and taps that may have stood idle. This guide lists the records an owner or general manager is expected to produce, who does each, and how often, from the fire logbook to the legionella scheme.

The fire risk assessment for sleeping accommodation is the document the fire service asks for first, and the test logs behind it are what they read second. An assessment that says the bedroom doors are checked monthly, with no monthly record, is a finding.

Why sleeping accommodation is different

Someone asleep in an unfamiliar room does not smell smoke, cannot see the exit signs, and wakes slowly and confused. The Fire Safety Order's standard is the same everywhere, to reduce the risk so far as is reasonably practicable, but what is reasonable where people sleep is more: automatic detection in every bedroom and corridor, linked so the whole building hears it; fire doors to every bedroom and onto the stairs, self-closing, with intact seals; a protected staircase; emergency lighting on every route; a fire action notice and a floor plan in every room; and staff on duty through the night who know the plan. The Home Office guide for sleeping accommodation sets it out; there is a shorter guide for small B&Bs and guest houses that is proportionate to a family house with three letting rooms.

The responsible person is the employer, in practice the general manager, and for a leased or managed hotel the owner as well for the parts they control. Two things in the record show that the duty is being discharged: that the assessment is current and specific to the building, and that the checks it relies on are logged, by name, on the dates it says.

Fire safety records

The logbook for a hotel is longer than for most buildings. Weekly alarm test from a different call point each time; the alarm serviced every six months by the contractor; monthly emergency lighting flick test and a yearly full-duration test; a monthly check of every fire door (closes fully from any angle, seals intact, gaps right, no wedges), which in a 40-bedroom hotel is 50 doors and a morning's work; escape routes and final exits walked daily; extinguishers checked monthly and serviced yearly.

Drills twice a year at least, and one of them should assume night conditions: the night porter alone, the alarm at three in the morning, who sweeps which floor. Training is recorded by name, on induction and yearly, and night staff, agency staff and housekeeping are the ones most often found missing from the register. Keep the fire safety information in each bedroom on the housekeeping inspection list; it goes missing.

Gas, electrics and the lift

Where paying guests sleep, the gas rules carry a legal interval: every gas appliance and flue checked by a Gas Safe registered engineer at least every twelve months, with the record kept for two years. It covers the central heating boiler, the kitchen range, gas fires in guest lounges and any gas water heater. Carbon monoxide alarms where there are gas or solid fuel appliances in sleeping rooms are expected.

Fixed wiring needs a periodic inspection and report, typically every five years; the report sets the next date. Portable appliances in guest rooms, kettles, hairdryers, irons, minibar fridges, are a large register and a frequent inspection finding; most hotels test them yearly. A passenger lift is lifting equipment under LOLER and needs a thorough examination every six months by a competent person, usually the insurer's engineer, with the report kept and any defects acted on by the date it gives.

Water safety

Hot water tanks, long pipe runs, showers in every room and rooms that stand empty midweek are the conditions legionella bacteria like. The HSE's Approved Code of Practice L8 asks for a written risk assessment by a competent person, a written scheme of control, and the monitoring it sets: usually monthly temperature checks at the calorifier and at sentinel taps (hot above 50°C within a minute, cold below 20°C within two), quarterly dismantling and descaling of shower heads, and flushing of outlets in rooms that have been unoccupied for a week. The records are a logbook like the fire one, and inspectors treat them the same way. A spa pool or swimming pool adds its own testing regime several times a day.

Kitchen, licence and the rest

If you serve food the restaurant records apply in full: the food safety management system and daily diary, allergen information, pest control, extraction cleaning to TR19 with the report kept. The restaurants and cafés guide has that list. The premises licence conditions, the employer's liability certificate, the accident book and RIDDOR reports, and the health and safety policy once you employ five or more people complete the set. If 200 or more people could be in the public areas at once, including staff, Martyn's Law applies and the four public protection procedures join the record.

Every record, at a glance

RecordHow oftenWho does it
Fire risk assessment, written, to the sleeping accommodation guideYearly, and after any refurbishment or change of useCompetent assessor, usually professional
Fire alarm test from a call point, loggedWeeklyDuty manager or maintenance
Fire alarm serviced, with certificateEvery 6 monthsAlarm contractor
Emergency lighting flick test, loggedMonthly; full-duration test yearlyMaintenance; yearly by an electrician
Fire doors to bedrooms and stairs checked (closing, seals, gaps)Monthly, every door, loggedMaintenance
Escape routes and final exits walkedDailyDuty manager
Fire extinguishers checkedMonthly visual; serviced yearlyMaintenance; yearly by a contractor
Fire drill, including a night-time scenarioAt least twice a year, covering every shiftResponsible person
Staff fire training including night staff, recorded by nameOn induction and at least yearlyGeneral manager
Fire safety information in every bedroomChecked on every room inspectionHousekeeping
Gas safety check, every appliance and flue, record kept 2 yearsEvery 12 monthsGas Safe registered engineer
Fixed wiring inspected (EICR)Typically every 5 yearsQualified electrician
Portable appliance testing (kettles, hairdryers, room fridges, kitchen)Risk-based; guest-room items often yearlyCompetent person or contractor
Legionella risk assessment and scheme of controlReviewed every 2 years or on changeCompetent person
Water temperature monitoring at sentinel outletsMonthlyMaintenance
Shower heads descaled; unused rooms flushedQuarterly; weekly for rooms standing emptyHousekeeping or maintenance
Passenger lift thorough examination (LOLER)Every 6 monthsInsurer's engineer or contractor
Kitchen extraction cleaned, with report (TR19)Every 3, 6 or 12 months by hours of useSpecialist contractor
Food safety management system and daily diaryDailyHead chef
Pool and spa water testing (if any)Several times a day, loggedTrained staff
Premises licence conditions; licence summary displayedKeep current; reviewed yearlyDesignated premises supervisor
Accident book and RIDDOR reportsAs they happenDuty manager
Employer's liability insurance certificate displayedYearly renewalOwner

Intervals are the legal minimum where one exists (gas, LOLER), otherwise the usual practice or the standard that applies. Your fire risk assessment, your legionella scheme and your contractors' reports may set shorter ones, and they take precedence.

Keeping them

Every entry needs a date and a name. The fire logbook lives at reception or in the duty office where the night manager can find it, and the fire service will ask to see it on the spot. The legionella logbook lives with maintenance. The certificates (gas, electrical, lift, alarm, extinguishers, extraction) are filed the day they arrive. Keep gas records for two years at least, fire and water records for three, accident records for three, and the certificates until the next one replaces them, with the old ones kept for the history. Most of all, keep a copy of everything in one place, because the fire officer, the environmental health officer and the insurer each want to see the whole picture, and the general manager who can show it in one sitting has a short inspection.

Common questions

Does a small B&B need a fire risk assessment?
Yes. If you take paying guests, the Regulatory Reform (Fire Safety) Order 2005 applies to the premises, however small, and since October 2023 the assessment must be recorded in writing. The Home Office published a guide specifically for small bed and breakfast, guest house and self-catering premises; its standards are proportionate to a family-run house, but they are not optional.
What is different about fire safety where people sleep?
People asleep do not smell smoke, cannot see the exit signs and take longer to react, in a building they do not know. So the standards are higher: detection in every bedroom and on every escape route, linked so the whole building hears it; fire doors to bedrooms that close on their own; emergency lighting on the routes; a protected staircase; and staff, including night staff, who know what to do. The sleeping accommodation guide is the longest of the government fire guides for that reason.
How often does a hotel need a gas safety check?
Every gas appliance and flue in a building where paying guests sleep must have a safety check by a Gas Safe registered engineer at least every twelve months, and the record kept for two years. That is a legal interval, not a recommendation, and it applies to the boiler and the kitchen alike.
Do we need a legionella risk assessment?
If the building has stored hot or cold water, showers, a spa pool or outlets that stand unused between guests, yes. The HSE's Approved Code of Practice L8 asks for a written risk assessment by a competent person, a scheme of control, and the monitoring records it calls for: usually monthly temperature checks at sentinel outlets, quarterly descaling of shower heads and flushing of rooms that have stood empty.
Does Martyn's Law apply to hotels?
Hotels are a listed use. Guest bedrooms are private and excluded; the lobby, bar, restaurant, function suite and spa are not, and the count is everyone who could be in those public areas at once, plus staff. A 60-bedroom hotel with a 200-seat function room clears the standard tier threshold comfortably. The pubs, restaurants and hotels guide works through the number.
Who is the responsible person in a hotel?
The employer, which is the operating company, and in practice the general manager. In a leased or managed hotel the owner also has duties for the parts they control. Name one person who keeps the record and one deputy, and make sure the night manager knows they are in charge of the building between midnight and six.

Fifty fire doors, twelve months of gas, three logbooks. One record.

The Venue Record keeps the assessment, the scheme and every certificate dated and on file, reminds the right person before each door check, water test, service and inspection falls due, logs each one from a phone with a second person's approval, and files the engineer's certificate the day they leave. When the fire officer asks, the whole record is one link.

Get early access

Opening to the first venues soon. Leave your email and you'll be first in.

A plain-English summary of the records a hotel, guest house or B&B is usually expected to keep in England and Wales, written for owners and managers. It is not legal advice and does not replace the guidance for your premises, the conditions on your licence, or the judgement of a competent person. The Venue Record is independent and is not connected to, endorsed by or approved by any fire and rescue authority, local authority or government body.

Regulation updates, monthly

What changed in premises safety regulation, what it means for a site like yours, and what if anything needs doing about it. We will email when the Martyn's Law commencement date is confirmed.

One email a month. Unsubscribe in one click. We do not pass your address to anyone.