Guide

Fire safety test frequencies

The routine checks a venue is expected to carry out, how often, and what goes in the logbook.

Last reviewed 4 August 2026.

The Fire Safety Order requires that fire safety equipment is subject to a suitable system of maintenance and kept in efficient working order. It does not set out frequencies. Those come from British Standards and from your own fire risk assessment, which is the authority for your building.

The intervals below are common practice, not law. Your fire risk assessment, your equipment manufacturer's instructions and the advice of a competent person take precedence over any general guidance, including this page.

Common intervals

CheckTypical intervalWho
Fire alarm call point testWeekly, rotating through call pointsSomeone on site
Fire alarm serviceAt least every six monthsCompetent person
Emergency lighting function testMonthly, short durationSomeone on site
Emergency lighting duration testAnnually, full rated durationCompetent person
Fire extinguisher visual checkMonthlySomeone on site
Fire extinguisher serviceAnnuallyCompetent person
Fire door checksCommonly quarterly or six-monthlySomeone on site
Escape route inspectionWeekly or before each eventSomeone on site
Fire risk assessment reviewAnnually, and after any material changeResponsible person
Fire drillAt least annuallyResponsible person

Fire alarm

The weekly test exists to confirm the system sounds and that at least one call point works. Use a different call point each week so that over time every one is tested. Record the call point used, the date, the person who did it, and whether the alarm sounded throughout the building.

For a hall used two evenings a week, "weekly" realistically means whenever someone is next in. Record the actual date rather than the intended one.

Emergency lighting

The monthly function test is a brief simulated power failure to confirm the lights come on. The annual test runs them for their full rated duration, commonly three hours, to confirm the batteries still hold.

The annual test is the one that catches ageing batteries, and it is the one most often skipped in small venues because it takes an evening. It is also the test an insurer will ask about after an incident.

Extinguishers

The monthly visual check is quick: is it there, is it in the right place, is the seal intact, is the gauge in the green, is it unobstructed. The annual service is carried out by a competent person and produces a certificate.

Fire doors

Check that the door closes fully onto the latch from any angle, that the seals are intact, that the hinges are secure and that nothing is wedging it open. Wedged-open fire doors are among the most common findings in community buildings, usually for entirely understandable reasons about ventilation or moving equipment.

Escape routes

Before any event, and weekly as routine: exits unobstructed and unlocked, routes clear, signage visible, external route to the assembly point passable. This is the check that takes two minutes and catches the stacked chairs.

What to record

Each entry should show what was checked, the date, who did it, the result, and any action taken. Missing entries are more damaging than entries recording a fault, because a gap looks like nothing happened while a recorded fault with a fix looks like a system working.

Whoever carries out the check should not be the only person who ever sees the logbook. A periodic review by a second named person catches drift.