Emergency lighting has to be maintained under the Fire Safety Order. The British Standards for it, BS 5266-1 and BS EN 50172, set the routine:
- a monthly function test: switch to emergency and check every light comes on;
- a yearly full-duration test: run on battery for the full rated time, usually three hours.
Record both.
The monthly test
Often called the flick test. Most fittings have a test switch, usually a key switch near the distribution board, that cuts the mains to the emergency lights without turning off the normal lighting circuit.
- Operate the test switch.
- Walk the building and check every emergency light and lit exit sign has come on.
- Restore the mains and check the charging indicators come back on.
- Write down the date, who did it, and any fitting that failed.
Keep the test short, a minute or so, just long enough to check each fitting. A volunteer can do it once shown how. Some systems test themselves automatically; someone still needs to check and record the results.
The yearly full test
Once a year the lights must run on battery for their full rated duration, normally three hours, and still be lit at the end. This shows the batteries can do the job in a real power cut.
- It’s usually done by an electrician or a fire protection company, who can replace failed batteries and lamps.
- Afterwards the batteries take up to 24 hours to recharge. Do it when the hall will be empty for a day, not before an evening booking.
- Get a written report or certificate, listing each fitting and the result.
Where emergency lighting is needed
Your fire risk assessment decides. Typically: escape routes and stairs, exits and exit signs, rooms without natural light, toilets without windows, near the fire alarm call points and firefighting equipment, and the kitchen. Exit signs that light up are part of the system and are tested the same way.
The records to keep
| Record | Includes |
|---|---|
| Monthly test log | Date, who tested, each failure and when it was fixed. |
| Yearly test report | Who did it, the duration, each fitting’s result. |
| Repairs | Batteries, lamps or fittings replaced. |
Our free emergency lighting log has a year of monthly and annual tests on one sheet.
Common questions
- How often should emergency lighting be tested?
- A short function test every month and a full-duration test, usually three hours, every year, following BS 5266-1 and BS EN 50172. Record both.
- Can a volunteer do the monthly emergency lighting test?
- Yes, once shown how to use the test switch and what to look for. The yearly full-duration test is usually done by an electrician or fire protection company.
- Why shouldn't the yearly test be done before an event?
- After running for three hours the batteries need up to 24 hours to recharge, so the lights wouldn't last a real power cut in the meantime.
- Do exit signs count as emergency lighting?
- Illuminated exit signs are part of the emergency lighting and are tested the same way.
The monthly test, remembered
The Venue Record sends the monthly emergency lighting test to whoever does it, logs it from their phone, and reminds you when the annual full-duration test and its certificate are due.
Set up emergency lighting checksSee it working first
No card needed to start. Then from £19 a month per building.
A plain-English summary for the people who run community buildings, not legal advice. Where your own fire risk assessment, lease, licence or insurer says something different, follow that.