Fixed wiring (EICR): no law sets an interval for a hall, but the wiring has to be kept safe. Industry guidance puts most halls and churches at five years, sooner if the electrician says so. The report gives the date of the next one.
Portable appliances (PAT): no law requires a yearly test. The law requires equipment to be safe; how often you check depends on the risk. For the kettles, urns and extension leads a hall’s hirers use hard, yearly testing is common practice.
Where the duty comes from
The Electricity at Work Regulations 1989 require electrical systems and equipment used at work to be maintained to prevent danger. They apply wherever there are employees, so a hall with a paid caretaker or cleaner is covered. Without employees, the Health and Safety at Work etc. Act 1974 and the hall’s duty to people using the building do the same job in practice.
Neither sets dates. The dates come from guidance: BS 7671 (the wiring regulations), the IET’s guidance on inspection and testing, and HSE’s advice on portable equipment. Insurers and licensing authorities often turn that guidance into a condition.
The fixed wiring: EICR
An Electrical Installation Condition Report is a periodic inspection of the fixed installation: the consumer unit, circuits, sockets, lighting and earthing. A qualified electrician inspects and tests, then gives the installation an overall verdict of satisfactory or unsatisfactory and lists anything that needs attention.
| Code | Means | What to do |
|---|---|---|
| C1 | Danger present | Make safe straight away. The electrician will usually do this on the day. |
| C2 | Potentially dangerous | Put right urgently. The report is unsatisfactory until it is. |
| FI | Further investigation needed | Get it investigated without delay. |
| C3 | Improvement recommended | Not a fail. Plan it in when you can. |
How often: most halls, churches and community centres work to five years, which is what guidance and most diocesan advice recommend for these buildings. A building with heavy use, a bar, outdoor supplies, or a history of problems may be given a shorter date. Whatever the report says for the next inspection is the date to work to.
Keep the full report, not just the front page. If it was unsatisfactory, keep the electrician’s confirmation that the C1 and C2 items were put right.
Portable appliances: PAT
PAT stands for portable appliance testing, and HSE is clear that the law doesn’t require every item to be tested every year. It requires equipment to be safe, and suggests intervals by type of equipment and how it’s used. There are three levels of check:
- User checks before use: look at the plug, the lead and the case. Anyone can do these, including hirers.
- Formal visual inspections by someone trained to know what to look for, recorded.
- Combined inspection and test with a tester, by a competent person, recorded and labelled.
In a hall, the kit that matters most is what’s used hard by people who don’t own it: the urn, kettles, the PA system, extension leads and anything in the kitchen. Testing those yearly is what most halls and insurers settle on. Equipment that hirers bring in is the hirer’s to keep safe; say so in the hire agreement.
Seasonal lights, such as the Christmas tree lights, should be checked before they go up each year. Take anything that fails out of use straight away.
The records to keep
- The latest EICR in full, with the date the next one is due.
- Confirmation that any C1, C2 or FI items were dealt with.
- The PAT register: each item, when it was inspected or tested, the result and who did it.
- A note of anything taken out of use.
A free portable appliance check log covers the visual checks between tests, with the six things to look for on the sheet.
Got the last electrical installation condition report (EICR)? Take a photo of it and The Venue Record reads the date, works out when the next inspection is due, and reminds you ahead of it. Read my certificate (starts a 14-day trial, no card needed).
Common questions
- Is an EICR a legal requirement for a village hall?
- No law sets a date for a hall, but the wiring has to be kept safe, and an EICR is how you show it. Five years is the usual interval for halls and churches, unless the electrician recommends sooner.
- Is PAT testing a legal requirement?
- No. The law requires electrical equipment to be maintained so it is safe. HSE says how often to inspect or test depends on the type of equipment and how it's used. Yearly testing of the hall's own heavily used items is common practice and often an insurance expectation.
- Can a volunteer do PAT testing?
- User checks and formal visual inspections can be done by a volunteer who knows what to look for. Testing with a PAT tester needs someone competent to use it and interpret the results; they don't have to be an electrician.
- What does C3 mean on an EICR?
- Improvement recommended. It isn't a fail and doesn't make the report unsatisfactory. C1 (danger present) and C2 (potentially dangerous) do.